ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
Page 76
REV 11 (ISS 08/03/2010)
System configuration: [various]
This menu is used to set the common functions of the panel. This section describes various other
options available in this menu.
The menu path is: Setup/System Configuration/[as below]. The following options are available
(see Table 23).
Table 23: Various system configuration setup options
Option Description
Silence delay
Allows the SILENCE ALARMS key to be delayed to prevent the alarm sounders from being
silenced (turned off) too soon, before being heard. Enter the required silence delay time
required in seconds.
Isolators
Define the quantity of isolators installed per Z-loop, range 0-16.
AGV (Alarm Group
Verification)
Specifies whether the Alarm Group Verification (AGV) function is enabled or disabled. Two
modes are provided:
Address group check - When enabled, the panel verifies that the correct device addresses
exist between loop isolators
Partial short check - When enabled, checks for partial short circuits and data corruption,
isolating the cause with the loop isolators
Time update
When this menu is [ENABLED], setting the time and date in a panel, which is part of a
network of panels, causes the time and date of all the panels in the network to be
updated.
Event time disp
Enabling this function causes the time of each alarm to be displayed on the LCD display.
This reduces the number of characters visible for the zone message by 6. See also
Zone
identification messages
on page 80
Flash healthy LED
With this function enabled, the LED's on sensors and line devices flash once every 20
seconds to indicate that the device is present and healthy. When a device is in alarm, the
LED flashes once every 2 seconds. With this function disabled, the LED's remain off when
the device is normal.
Zone LED link
The zone LED's can be set to be automatically linked to the system zones, or to be
programmed to different zones with I/O-mapping. This menu defines whether the zone
LED's are zone-linked or programmable.
Time set level
This function enables either free access to the "set time" facility, or limits access to access
level 2.
Control k/switch
This function causes the RDU’s Controls Enable/Disable keyswitch to be linked to the level
2 access code, allowing it to be used for level 2 access from RDU’s, which do not have
keypads with which to enter a passcode.
Note:
For this to operate, the RDU’s Control’s key switch must be wired into the
required “Reserved terminal” of its display board in place of the “Controls Off”
terminal.