CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–13
To set the ground CT ratings, modify the
S2 SYSTEM SETUP
ZV
CURRENT SENSING
ZV
GROUND CT
and the
S2 SYSTEM SETUP
ZV
CURRENT SENSING
ZV
GROUND CT PRIMARY
settings as shown below.
Z
Press the
MENU
key until the relay displays the Settings menu header.
SETTINGS
[
Press
MESSAGE
X
or
ENTER
SETTINGS
[
Press
MESSAGE
T
SETTINGS
[
Press
MESSAGE
X
or
ENTER
CURRENT
[
Press
MESSAGE
X
or
ENTER
PHASE CT PRIMARY:
600 A
Press
MESSAGE
T
MOTOR FULL LOAD
AMPS
Press
MESSAGE
T
GROUND CT:
Multilin CT 50/
Press the
VALUE
keys until
“5 A Secondary” is displayed.
GROUND CT:
5 A Secondary
Press the
ENTER
key to store the
settings.
NEW SETTINGS
HAS
Press
MESSAGE
T
GROUND CT PRI-
MARY:
Press the
VALUE
keys until 50 A is
displayed, or enter the value directly via
the numeric keypad.
GROUND CT PRI-
MARY:
Press the
ENTER
key to store the
settings.
NEW SETTINGS
HAS
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...