3–8
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
3.1.6
DeviceNet Connection
If using the 469 DeviceNet option (Refer to GEK-106491C:
469 Communications Guide)
,
ensure that the network cable is disconnected from the rear terminal block before
removing the unit out of the case to prevent any damage to the connector.
The unit may also be removed from the case with the network cable connector still
attached to the rear terminal block provided that there is at least 16" of network cable
available when removing the unit out of the case. This extra length will allow the network
cable to be disconnected from the terminal block from the front of the switchgear panel.
Once disconnected, the cable can be left hanging safely outside the case for re-inserting
the unit back into the case.
The unit may then be re-inserted by first connecting the network cable to the units' rear
terminal block (see step 3 of
Ensure that the network cable does not get caught inside the case while sliding in the
unit. This may interfere with proper insertion to the case terminal blocks and damage
the cable.
The DeviceNet port has the following characteristics:
• Connector type: 5-pin Phoenix connector
• Baud rate: 125K, 250K or 500K baud
• Protocol: DeviceNet
The following ports available simultaneously:
• RS232, 2
×
RS485/422 with no DeviceNet option
• RS232, 1
×
RS485/422 with DeviceNet option
The DeviceNet configuration is shown in the following table:
Pin
Signal
Description
1
V–
Negative supply voltage
2
CAN_L
CAN_L bus line
3
SHIELD
Cable shield
4
CAN_H
CAN_H bus line
5
V+
Positive supply voltage
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...