CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–11
6.3
A2 Metering Data
6.3.1
Current Metering
PATH: ACTUAL VALUES
ZV
A2 METERING DATA
Z
CURRENT METERING
All measured current values are displayed here. The
CURRENT UNBALANCE
is defined as the
ratio of negative-sequence to positive-sequence current,
I
2
/
I
1
when the motor is
operating at a load (
I
avg
) greater than FLA. If the motor
I
avg
is less than FLA, unbalance is
defined as
I
2
/
I
1
×
I
avg
/ FLA. This derating is necessary to prevent nuisance alarms and
trips when a motor is lightly loaded. The
U/B BIASED MOTOR LOAD
value shows the
equivalent motor heating current caused by the unbalance
k
factor.
CURRENT
[
Z
]
METERING
A:
0
B:
0
C:
0
Amps
Range: 0 to 100000 A
MESSAGE
AVERAGE PHASE
CURRENT: 0 Amps
Range: 0 to 100000 A
MESSAGE
MOTOR LOAD:
0.00 x FLA
Range: 0.00 to 20.00 x FLA
MESSAGE
CURRENT UNBAL-
ANCE:
MESSAGE
U/B BIASED MOTOR
LOAD: 0.00 x FLA
Range: 0.00 to 20.00 x FLA
MESSAGE
GROUND CURRENT:
0.00 Amps
Range: 0.00 to 5000.00 A. Not seen if
Ground CT is set as “None”.
MESSAGE
A:
0
B:
0
Range: 0 to 5000 A. Seen if Phase
Differential CT has 1A/5A
Secondary
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...