CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–15
2.2.10 Physical
CASE
Type: .....................................................................Fully drawout (automatic CT shorts)
Seal: ......................................................................Seal provision
Mounting:...........................................................Panel or 19-inch rack mount
IP Class:...............................................................IP40-X
PACKAGING
Shipping box:....................................................12”
×
11”
×
10” (W
×
H
×
D)
30.5 cm
×
27.9 cm
×
25.4 cm
Shipping weight: ............................................17 lbs Max / 7.7 kg
TERMINALS
Low voltage (A, B, C, D terminals):
12 AWG maximum
High voltage (E, F, G, H terminals):
#8 ring lug, 10 AWG wire std.
2.2.11 Environmental
ENVIRONMENT
Ambient operating temperature:
–40°C to +60°C
Ambient storage temperature:
–40°C to +80°C
Humidity:............................................................up to 90%, non-condensing.
Altitude:...............................................................up to 2000 m
Pollution degree: ............................................2
Note
At temperatures less than –20°C, the LCD contrast may be impaired.
2.2.12 Long-term Storage
LONG-TERM STORAGE
Environment: ....................................................In addition to the above environmental considerations,
the relay should be stored in an environment that is dry,
corrosive-free, and not in direct sunlight.
Correct storage:..............................................Prevents premature component failures caused by
environmental factors such as moisture or corrosive
gases. Exposure to high humidity or corrosive
environments will prematurely degrade the electronic
components in any electronic device regardless of its use
or manufacturer, unless specific precautions, such as
those mentioned in the Environment section above, are
taken.
Note
It is recommended that all relays be powered up once per year, for one hour
continuously, to avoid deterioration of electrolytic capacitors and subsequent relay
failure.
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...