1–4
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
c.
Learned and last starting capacity.
d. Average motor load.
4.
Maintenance data. This is useful statistical information that may be used for
preventive maintenance. It includes:
a. Trip counters
b. General counter such as number of motor starts, number of emergency restarts,
number of starter operations, digital counter for other purposes not listed above.
c.
Timers such as motor running hours, time between starts timer, and five start tim-
ers used to calculate the average start time of the motor.
5.
RTD Learned Data, which includes the maximum temperature measured by each of
the 12 RTDs.
6.
Event recorder downloading tool.
7.
Product information including model number, firmware version, additional product
information, and calibration dates.
8.
Oscillography downloading tool.
Alarm, trip conditions, diagnostics, and system flash messages are grouped under
Target
Messages
.
Z
Press the
MENU
key to access the header of each menu, which will be
displayed in the following sequence:
To access settings,
Z
Press the
MENU
key until the display shows the header of the Settings
menu.
Z
Press the
MESSAGE
X
or
ENTER
key to display the header for the first
Settings page.
The Settings pages are numbered, have an ‘S’ prefix for easy
identification and have a name which provides a general idea of the
settings available in that page.
Pressing the
MESSAGE
T
and
MESSAGE
S
keys will scroll through all
the available Settings page headers. Settings page headers look as
follows:
SETTINGS
[
Z
]
ACTUAL
VALUES
[
Z
]
TARGET
MESSAGES [
Z
]
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...