![GE Multilin 469 Instruction Manual Download Page 255](http://html.mh-extra.com/html/ge-multilin/469/469_instruction-manual_572026255.webp)
CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–5
6.2.2
Motor Status
PATH: ACTUAL VALUES
Z
A1 STATUS
ZV
MOTOR STATUS
These messages describe the motor status at any given point in time. If the motor has
been tripped and the 469 has not yet been reset, the
MOTOR STATUS
value will be “Tripped”.
The
MOTOR THERMAL CAPACITY USED
reflects an integrated value of both the Stator and
Rotor Thermal Capacity Used. The values for
ESTIMATED TRIP TIME ON OVERLOAD
appear
whenever the 469 picks up on the overload curve.
6.2.3
Last Trip Data
PATH: ACTUAL VALUES
Z
A1 STATUS
ZV
LAST TRIP DATA
MOTOR
STATUS
[
Z
]
MOTOR STATUS:
Stopped
Range: Tripped, Stopped, Starting,
Running, Overload
MESSAGE
MOTOR THERMAL
CAPACITY USED: 0%
Range: 0 to 100%
MESSAGE
ESTIMATED TRIP
TIME
Range: 0 to 10000 sec., Never
MESSAGE
MOTOR SPEED:
Low Speed
Range: HIgh Speed, Low Speed. Seen if
two speed motor is enabled
LAST
TRIP
[
Z
]
DATA
CAUSE OF LAST
TRIP:
No Trip to Date
Range: see below
MESSAGE
TIME OF LAST
TRIP:
Range: hour:min:sec
MESSAGE
DATE OF LAST
TRIP:
Range: Month Day Year
MESSAGE
MOTOR SPEED DUR-
ING
Range: High Speed, Low Speed. Seen if
two-speed motor is enabled
MESSAGE
TACHOMETER
PreTrip: 3600 RPM
Range: 0 to 3600 RPM. Seen if a Digital
Input set as Tachometer.
MESSAGE
A:
0
B:
0
Range: 0 to 100000 A
MESSAGE
MOTOR LOAD:
0.00 x FLA Pre-
Range: 0.00 to 20.00 x FLA
MESSAGE
CURRENT UNBALANCE
PreTrip: 0%
Range: 0 to 100%
MESSAGE
GROUND CURRENT
PreTrip: 0.00
Range: 0.0 to 5000.0 A. Not seen if
Ground CT is set to “None”.
MESSAGE
A:
0
B:
0
C:
0
A
Range: 0 to 5000 A. Not seen if
Differential CT is set as None
MESSAGE
HOTTEST STATOR
RTD
Range: –50 to 250°C or –58 to 482°F.
Seen only if at least 1 RTD is set
as Stator
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...