CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–39
forgotten, contact the factory with the encrypted access code. See
5–8 for passcode features.
•
ACCESS DENIED, SHORT ACCESS SWITCH:
In order to store any settings values, the
access switch must be shorted. If this message appears and it is necessary to change
a settings, short access terminals C1 and C2.
•
ALL POSSIBLE RESETS HAVE BEEN PERFORMED:
If only some of the trip and alarm
features that are active can be cleared (i.e. the conditions that caused some of these
trips and/or alarms are still present), then this message will appear when a RESET is
performed, indicating that only trips and alarms that could be reset have been reset.
•
ARE YOU SURE? PRESS [ENTER] TO VERIFY:
If the
RESET
key is pressed and resetting
of any trip or alarm feature is possible, this message will appear to ask for verification
of the operation. If
RESET
is pressed again while the message is still on the display, the
reset will be performed.
•
DATA CLEARED SUCCESSFULLY:
This message confirms that data has been cleared or
reset in the
S1 469 SETUP
ZV
CLEAR DATA
or
S1 469 SETUP
ZV
INSTALLATION
settings
groups.
•
DATE ENTRY WAS NOT COMPLETE:
Since the
DATE
settings has a special format (MM/
DD/YYYY), if
ENTER
is pressed before the complete value is entered, this message
appears and the new value is not stored. Another attempt will have to be made with
the complete information.
•
DATE ENTRY WAS OUT OF RANGE:
This message appears if and invalid entry is made
for the
DATE
(e.g. 15 entered for month).
•
DEFAULT MESSAGE HAS BEEN ADDED:
Any time a new default message is added to
the default message list, this message will appear as verification.
•
DEFAULT MESSAGE HAS BEEN REMOVED:
Any time a default message is removed
from the default message list, this message will appear as verification.
•
DEFAULT MESSAGE LIST IS FULL:
If an attempt is made to add a new default message
to the default message list when 20 messages are already assigned, this message will
appear. In order to add a message, one of the existing messages must be removed.
•
DEFAULT MESSAGES 6 of 20 ARE ASSIGNED:
This message appears each time the
S1
469 SETUP
ZV
DEFAULT MESSAGES
settings group is entered. It notifies the user of the
number of assigned default messages.
•
END OF LIST:
This message will indicate when the bottom of a subgroup has been
reached.
•
END OF PAGE:
This message will indicate when the bottom of a page has been
reached.
•
ENTER NEW PASSCODE FOR ACCESS:
If the passcode is zero, the passcode security
feature is disabled. If the Change Passcode settings is entered as yes, this flash
message will appear prompting the user to enter a non-zero passcode which in turn
will enable the feature.
•
INPUT FUNCTION IS ALREADY ASSIGNED:
The Assignable Digital Input functions may
only be used once. If an attempt is made to assign the same function to two different
switches, this message will appear.
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...