5–100
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.14.3 Fault Setup
PATH: SETTINGS
ZV
S13 469 TESTING
ZV
FAULT SETUP
The values entered under Fault Values will be substituted for the measured values in the
469 when the simulation mode is “Simulate Fault”.
FAULT
[
FAULT CURRENT
PHASE A: 0.00 x
Range: 0.00 to 20.00 x CT in steps of
0.01
MESSAGE
FAULT CURRENT
PHASE B: 0.00 x
Range: 0.00 to 20.00 x CT in steps of
0.01
MESSAGE
FAULT CURRENT
PHASE C: 0.00 x
Range: 0.00 to 20.00 x CT in steps of
0.01
MESSAGE
FAULT GROUND
CURRENT: 0.0 A
Range: 0.0 to 5000.0 A in steps of 0.1
MESSAGE
FAULT VOLTAGES
VLINE: 1.00 x
Range: 0.00 to 1.10 x RATED in steps of
0.01
MESSAGE
FAULT CURRENT
LAGS VOLTAGE: 0°
Range: 0 to 359° in steps of 1
MESSAGE
FAULT DIFF AMPS
IDIFF: 0.00 x CT
Range: 0.00 to 1.10 x RATED in steps of
0.01
MESSAGE
FAULT STATOR
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT BEARING
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT OTHER
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT AMBIENT
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT SYSTEM
FREQUENCY: 60.0
Range: 45.0 to 70.0 Hz in steps of 0.1
MESSAGE
FAULT ANALOG
INPUT 1: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 2: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 3: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 4: 0%
Range: 0 to 100% in steps of 1
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...