469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Pressure Switch Alarm
PATH: SETTINGS
ZV
S3 DIGITAL INPUTS
ZV
ASSIGNABLE INPUT 1(4)
These settings apply only if the
INPUT 1(4) FUNCTION
is “Pressure Sw. Alarm”.
Once the pressure switch alarm function is chosen for one of the assignable digital inputs,
the settings messages shown here will follow the assignment message. The Pressure
Switch alarm feature may be blocked for a specified period of time from a motor start. A
value of zero for the block time indicates that the feature is always active, when the motor
is stopped or running. After the block delay has expired, the digital input will be monitored.
If a closure occurs, after the specified delay, an alarm will occur.
Pressure Switch Trip
PATH: SETTINGS
ZV
S3 DIGITAL INPUTS
ZV
ASSIGNABLE INPUT 1(4)
These settings apply only if the
INPUT 1(4) FUNCTION
is “Pressure Switch Trip”.
Once the Pressure Switch Trip function is chosen for one of the digital inputs, the settings
messages shown here will follow the assignment message. The Pressure Switch Trip
feature may be blocked for a specified period of time from a motor start. A value of zero for
the Block time indicates that the feature is always active, when the motor is stopped or
running. After the block delay has expired, the digital input will be monitored. If a closure
occurs, after the specified delay, a trip will occur.
ASSIGNABLE
[
INPUT 1 FUNCTION:
Pressure Sw Alarm
Range: See above
MESSAGE
BLOCK PRES. SW.
ALARM
Range: 0 to 5000 s in steps of 1
MESSAGE
PRESSURE SWITCH
ALARM: Unlatched
Range: Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS:
Range: Alarm, Alarm & Auxiliary2,
Alarm & Auxiliary2 & Aux3,
Alarm & Auxiliary3, Auxiliary2,
Aux2 & Aux3, Auxiliary3
MESSAGE
PRESSURE SW.
ALARM
Range: 0.1 to 100.0 sec., step: 0.1
MESSAGE
PRESSURE SW.
ALARM
Range: On, Off
ASSIGNABLE
[
INPUT 1 FUNCTION:
Pressure Switch
Range: See above
MESSAGE
BLOCK PRES. SW.
TRIP
Range: 0 to 5000 sec.; step: 1
MESSAGE
ASSIGN TRIP
RELAYS:
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
PRESSURE SW. TRIP
DELAY: 5.0 s
Range: 0.1 to 100.0 s in steps of 0.1
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...