Service Manual MCC Cold US 20220700
Page 57
Parameter
Description
Value
Unit
SEt
Temperature Setpoint
1
°C
Compressor ("CP" folder)
diF
Compressor relay activation differential
1
°C
HSE
Maximum value that can be assigned to the Setpoint
5
°C
LSE
Minimum value that can be assigned to the Setpoint
-1
°C
Ont
Controller on time for faulty probe
0
min
Oft
Controller off time for faulty probe
1
min
dOn
Compressor relay activation delay after request
0
secs
dOF
Deflay after switching off and subsequent activation
0
min
dbi
Delay between two concescutive compressor activations
2
min
OdO
Delay in activating outputs after the instrument is switched on or after a
power failure
0
min
dFA
Delay fimte in activating compressor and condenser fans after request
0
secs
Defrost ("dEF" folder)
dty
Type of defrost (0 = electrical, 1 = reverse cycle, 2 = "Free")
0
num
dit
Interval between the start of two consecutive defrost cycles
3
hours
dCt
Selects the count mode for the defrost interval
1
num
dOH
Defrost start delay time after request
0
min
dEt
Defrost timeout; determines the maximum defrost duration
30
min
dSt
Defrost end temperature (determiend by evaporator probe)
4
°C
dPO
Determines whether the instrument must enter defrost mode
y
flag
dSE
Temperature threshold for start of defrost
0
°C
dtt
Time for which the temperature of the evaporator must remain below dSE
0
min
Fan regulator ("Fan" folder)
FPt
Characterizes the "Fst" parameter
0
flag
FSt
Fan stop temperature
50
°C
Fad
Fan starting differential
1
°C
Fdt
Fan activation delay after a defrost cycle
0
min
dt
Coil drainage time
0
min
dFd
Allows to select the evaporator probes exclusion during defrost
n
flag
FCO
Evaporator fans operating mode
1
num
FdC
Evaporator fans switch-off delay after compressor disabled
0
min
Fon
Fans ON time in duty cycle
12
secs*10
FoF
Fans OF time in duty cycle
6
secs*10
Fnn
Fans ON time in night duty cycle
1
secs*10
FnF
Fans OF time in night duty cycle
12
secs*10
Alarms ("AL" folder)
Att
Parameters HAL and LAL
0
num
AFd
Alarm differential
2
°C
HAL
Maximum temperature alarm
10
°C
LAL
Minimum temperatre alarm
-30
°C
8.1
Parameter MCC Cold Settings (Self Serve)
Summary of Contents for MCC 120
Page 4: ...Page 4 Service Manual MCC Cold US 20220700...
Page 20: ...Page 20 Service Manual MCC Cold US 20220700 4 1 Connecting drain or evaporation tray...
Page 21: ...Service Manual MCC Cold US 20220700 Page 21 4 1 Connecting drain or evaporation tray...
Page 30: ...Page 30 Service Manual MCC Cold US 20220700 5 1 MCC 90 Drop in Dimensions Self Serve...
Page 39: ...Service Manual MCC Cold US 20220700 Page 39 6 0 Installation Front door section first version...
Page 83: ...Service Manual MCC Cold US 20220700 Page 83...
Page 87: ...Service Manual MCC Cold US 20220700 Page 87...
Page 89: ...Service Manual MCC Cold US 20220700 Page 89 Page intentionally left blanc...
Page 102: ...Page 102 Service Manual MCC Cold US 20220700 13 0 Electrical schematics MCC Cold first version...
Page 104: ...Page 104 Service Manual MCC Cold US 20220700 13 2 Electrical wiring MCC Cold Self Serve N L...