2.8 Setting I/O Master Wire Replacement Parameters
To enable I/O functionality in the I/O Master, set the
Enable I/O
option in the
IO Settings
tab to
Enabled
.
Note
: This setting is available in option
0
in the
FGRIO Setup
menu in the terminal interface.
After enabling I/O, set these parameters in the IO Settings tab.
l
Sensor Power
l
Default Delay
l
Default Output
Use the
Analog Out
and
Digital Out
fields in the
IO Settings
tab to map the I/O Master's outputs
to the I/O Slave inputs.
Note
: For more information about mapping analog and digital outputs, see
Outputs to I/O Slave Inputs (on page 42)
.
2.8.1 Default Delay
Default Delay
Setting
Description
Default Setting:
255
Options:
Any number between 0 and 255, representing 0.28 second units (see below)
Terminal Menu:
(9) FGRIO Setup > (9) Timeout
Description:
Determines the amount of time to wait before issuing a Link Alarm due to loss
of communication between the I/O Master and /IO Slave.
The value is set in 0.28 second units.
Example
: A value of 36 represents 36 x 0.28 = 10.08 seconds.
Set between 0 and 255 using these examples as guidelines:
l
1 = 0.28 seconds
l
4 = 1.12 seconds
l
25 = 7 seconds
l
255 = 71.4 seconds