3. Configuring an I/O Slave
Default Delay
Setting
Description
Set between 0 and 255 using these examples as guidelines:
l
1 = 0.28 seconds
l
4 = 1.12 seconds
l
25 = 7 seconds
l
255 = 71.4 seconds
3.7.5 Digital Output 1 Default and Digital Output 2 Default
Digital Output 1 Default and Digital Output 2 Default
Setting
Description
Default Setting:
Output ON
Options:
l
Output On - Energized. Contact to ground is closed. (Conducting to GND,
2 Amps max)
l
Output Off - Not energized. Contact open.
l
No Change - Make no change in state when communication is lost.
Terminal Menu:
(9) FGRIO Setup > (3) Digital Def1 and (4) Digital Def2
Description:
Sets the state the Digital Output returns to when the device is powered up or
when the device loses its link to the Master in the network.
Note
: If programming a Digital Output to turn on after it loses a link,
verify the energized device can sustain the state undamaged, in case
the loss is lengthy.
3.7.6 DI1 Pullup and DI2 Pullup
DI1 Pullup and DI2 Pullup
Setting
Description
Default Setting:
Pullup
Options:
l
Pullup - The 10 KΩ internal resistor attached to the input is connected to
the 3.3 V logic supply to provide a pull up for connecting closed-contact-
to-GND sensors.
l
Pulldown - The 10 KΩ internal resistor attached to the input is connected
to GND to provide a pull up for connecting closed-contact-to-voltage
sensors.