2. Configuring an I/O Master
2.8.2 Default Output
Default Output
Setting
Description
Default Setting:
Unchanged
Options:
l
On - Returns the outputs to an On state.
l
Off - Returns the output to an Off state.
l
Unchanged - The outputs remain at the state they were in when the
communication was lost.
Terminal Menu:
(9) FGRIO Setup > Default Output
Description:
l
Sets the state the output returns to when you power up the device, or the
device loses its link with the instrument to which it is attached.
l
The outputs return to this state after the amount of time has passed in the
Default Delay parameter.
2.8.3 Mapping I/O Master Outputs to I/O Slave Inputs
Map the I/O Master Outputs to the I/O Slave inputs to match the network wiring.
Note
: The I/O mapping fields are available in the
I/O Settings
tab in
Tool Suite
and the
FGRIO
Setup
menu in the terminal interface.
Figure 7: Mapping Diagram
Page 42 of 131
LUM0008AG Rev Sep-2015
This document is the property of FreeWave Technologies, Inc. and contains proprietary information owned by
FreeWave®. This document cannot be reproduced in whole or in part by any means without written permission from
FreeWave Technologies, Inc.
Summary of Contents for FGR2-IO-IOE
Page 131: ......