![FreeWave FGR2-IO-IOE User Manual And Reference Manual Download Page 26](http://html1.mh-extra.com/html/freewave/fgr2-io-ioe/fgr2-io-ioe_user-manual-and-reference-manual_2331115026.webp)
2. Configuring an I/O Master
2.1 Configuring an I/O Master
This section describes how to quickly get the I/O Master in a wire replacement I/O network setup
and communicating with the I/O Slaves.
Note
: It covers only the settings required for radio communication to and from the I/O Master and the
I/O Slaves.
Parameter settings NOT included in this procedure can be changed or remain at the factory default
setting.
1. Connect the radio to the serial port of a computer either through a serial cable or using the
diagnostics cable.
2. Connect the radio to a power source (+7.0 to +30.0 VDC).
3. Open
Tool Suite
and click
Configuration
in the
Application
pane.
4. Click
Read Radio
to read the radio's current settings.
Figure 6:
Tool Suite
Radio Information tab
5. Click the
Operation Mode
tab.
6. In the
Modem Mode
field, select one of these options:
l
(E) FGRIO Master
- Select this mode when the I/O Master is a standalone I/O
system and is connected to only I/O Slaves.
l
(3) Point to MultiPoint Slave
- Select this option if the I/O Master is part of a larger
network and serves as a MultiPoint Slave that is connected to the I/O Slaves.
Configure the other, non-modbus radios in the network accordingly.
7. Verify the
Repeaters
parameter is set to
Enabled
in the serial network Master.