48
Whenever a logger on the network is in alarm status, the external
alarm will be activated. Refer to section
3.7.6 for more details.
3.7.
Data Logger Sensor
Overview
This section provides an overview of the hardware
specifications of the DataNet data loggers.
3.7.1.
Internal Sensor Types
The DNL810, DNL910, DNL920, DNL910-PA and DNL920-PA
loggers include internal sensors, depending on the logger
model.
Sensor
Measurement
Range
Accuracy
Logger
Model
Digital Humidity
5% to 95%
±3% (in DataNet
software)
±4% (on logger LCD)
DNL920
DNL920-PA
DNL810
±0.5 ºC
DNL920
DNL920-PA
Digital Temperature -20 ºC to 50 ºC
±0.4 ºC
DNL810
Temperature
PT100
-20 ºC to 50 ºC
±0.3 ºC
DNL910
DNL910-PA