Rosemount Model 3095FT HART Flow Transmitter
4-36
Maintenance
Maintenance Modes
When the User Interface Maintenance Modes screen is selected, the
current Model 3095FT operation mode is indicated by the filled bullet
(see Figure 4-26).
To change to a different mode, select the desired mode, then select Ok.
Changing between maintenance modes typically takes 20 seconds to
complete.
The standard operation mode is “On-line Normal Operation.” When the
transmitter is in this mode, the audit trail data and the current
configuration can be read from the transmitter, but sending a
configuration to the transmitter and all sensor trim maintenance tasks
are prevented.
NOTE
All maintenance and configuration tasks, except On-Line Maintenance
Modes, are prevented when the WP (write protect) switch is set to ON.
See Page 2-4 to change this switch to OFF.
When the transmitter is in any of the four maintenance modes, sending
a configuration file and performing sensor trim maintenance tasks are
allowed. On-line maintenance is typically used when gas is flowing in
the line, while off-line maintenance is typically used when the gas flow
has stopped.
When the transmitter is placed into “Off-line Maintenance,” an event
log is generated, and all Model 3095FT flow calculations and logging
activities stop.
In addition, before the Model 3095FT User Interface Software places
the transmitter into off-line maintenance, a message is displayed.
3
0
9
5
-3
095
00
25
30
95-
30
950
04
2
Summary of Contents for 3095FT
Page 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Page 2: ......
Page 4: ......
Page 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Page 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Page 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Page 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Page 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Page 149: ...A 3 Appendix A...
Page 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Page 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Page 153: ...B 3 Appendix B...
Page 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Page 155: ...B 5 Appendix B...
Page 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Page 157: ...B 7 Appendix B...
Page 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Page 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Page 161: ...C 3 Appendix C...
Page 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Page 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Page 165: ...D 3 Appendix D...
Page 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Page 167: ...D 5 Appendix D...
Page 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Page 183: ......