4-35
Using the Model 3095FT User Interface Software
Maintenance
Transmitter
EEPROM Info
Selecting EEPROM Info does not display any screens, but performs
advanced troubleshooting data gathering that can only be interpreted
by the factory.
When directed by a Rosemount Customer Central technical
representative, perform the following tasks to gather this data.
1. Select Maintenance, Transmitter, then select EEPROM Info.
2. Select Logs, then select Collect Configuration.
3. Gather your typical log information. (For example, if you typically
gather 30 days of log data, then retrieve 30 days of data.)
4. Select Sys Admin, then select Comm Statistics.
5. Select Sys Admin, then select Comm Options.
6. Using File Manager (or the DOS prompt), copy the following files
from the 3095FT working directory to a floppy disk:
\comm.sts
\3095ui.ini
\
filename
.log\xmitter.dmp
\
filename
.log\xmitter.cfg
\
filename
.log\xmitter.day
\
filename
.log\xmitter.var
\
filename
.log\xmitter.evt
7. Send the floppy disk containing these files to Rosemount as
directed by Rosemount Customer Central.
Maintenance
Clock
Since flow is a time-based measurement and gas billings are based on
time, it is extremely important that the Model 3095FT transmitter
contains the current time and date.
The simplest method to set the Model 3095FT time is to verify that the
“Current PC Date and Time” is correct, then click “Use PC Date/Time”
(see Figure 4-25).
Alternatively, type in the correct date and time in the six boxes, then
click ok.
FIGURE 4-25. Clock Screen.
3
095
-3
095
00
15
Summary of Contents for 3095FT
Page 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Page 2: ......
Page 4: ......
Page 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Page 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Page 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Page 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Page 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Page 149: ...A 3 Appendix A...
Page 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Page 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Page 153: ...B 3 Appendix B...
Page 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Page 155: ...B 5 Appendix B...
Page 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Page 157: ...B 7 Appendix B...
Page 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Page 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Page 161: ...C 3 Appendix C...
Page 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Page 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Page 165: ...D 3 Appendix D...
Page 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Page 167: ...D 5 Appendix D...
Page 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Page 183: ......