7-3
Specifications and Reference Data
Humidity limits
0–100% relative humidity.
Turn-on Time
Process variables will be within specifications less than 60 seconds
after power is applied to transmitter.
Damping
Response to step input change can be user-selectable from 0 to 7
seconds for one time constant. This is in addition to sensor response
time of 0.2 seconds.
Real-Time Clock Accuracy
±2 minutes per month at reference conditions.
MODEL 3095FT
PERFORMANCE
SPECIFICATIONS
Differential Pressure
Range 2
0–2.5 to 0–250 inH
2
O (0–0.62 to 0–62.2 kPa)
(100:1 rangeability is allowed).
(Zero-based spans, reference
conditions, silicone oil fill,
316 SST isolating diaphragms,
and digital trim values equal
to the span end points.)
Reference Accuracy
(including Linearity, Hysteresis, Repeatability)
±0.075% of span for spans from 1:1 to 10:1 of URL
For spans less than 10:1 rangedown,
Ambient Temperature Effect per 50 °F (28 °C)
±(0.025% URL + 0.125% span) spans from 1:1 to 30:1.
±(0.035% URL – 0.175% span) spans from 30:1 to 100:1.
Static Pressure Effects
Zero error = ±0.10% of URL per 1,000 psi (6894 kPa).
Span error = ±0.20% of reading per 1,000 psi (6894 kPa).
Stability
±0.1% of URL for 12 months.
Absolute Pressure
Range 3: 0–8 to 0–800 psia (0–55.16 to 0–5515.8 kPa)
(100:1 rangeability is allowed).
Range 4: 0–36.26 to 0–3,626 psia (0–250 to 0–25000 kPa)
(100:1 rangeability is allowed).
Reference Accuracy
(including Linearity, Hysteresis, Repeatability)
±0.075% of span for spans from 1:1 to 6:1 of URL.
For spans less than 6:1 rangedown,
Ambient Temperature Effect per 50 °F (28 °C)
±(0.05% URL + 0.125% span) spans from 1:1 to 30:1.
±(0.06% URL – 0.175% span) spans from 30:1 to 100:1.
Stability
±0.1% of URL for 12 months.
Accuracy
0.025
0.005
URL
Span
------------
+
% of Span
=
Accuracy
0.03
0.0075
URL
Span
------------
+
% of span
=
Summary of Contents for 3095FT
Page 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Page 2: ......
Page 4: ......
Page 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Page 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Page 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Page 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Page 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Page 149: ...A 3 Appendix A...
Page 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Page 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Page 153: ...B 3 Appendix B...
Page 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Page 155: ...B 5 Appendix B...
Page 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Page 157: ...B 7 Appendix B...
Page 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Page 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Page 161: ...C 3 Appendix C...
Page 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Page 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Page 165: ...D 3 Appendix D...
Page 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Page 167: ...D 5 Appendix D...
Page 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Page 183: ......