Rosemount Model 3095FT HART Flow Transmitter
4-18
Configuration
Flow
Gas Properties (N2)
The displayed gas properties screen is determined by the calculation
method selected in the Flow Parameters screen. If “AGA8 Gr-CO2-N2”
is selected, then the Gross Characterization Method, Option 2, is
displayed (Figure 4-7a). This method requires the entry of real gas
specific gravity, CO2 mole percent, and N2 mole percent, and also
allows entry of H2 mole percent, CO mole percent, and heating value.
H2 and CO are typically zero for natural gas applications.
NOTE
This gross characterization method does not require heating value.
However, heating value is required if energy rates or totals are to be
logged or displayed on the LCD meter.
The valid ranges for the Gas Properties (N2) screen selections are:
Real gas relative density (specific gravity) at base conditions
0.554000–0.900000.
CO2 (carbon dioxide) mole percent
0–30 percent.
N2 (nitrogen) mole percent
0–50 percent.
H2 (hydrogen) mole percent
0–10 percent.
CO (carbon monoxide) mole percent
0–3 percent.
Volumetric Gross Dry Heating Value at base conditions
477–1200 BTU/SCF.
30
95-
309
50
003
FIGURE 4-7a. Gas Properties Screen
(AGA8 Gr-CO2-N2).
Summary of Contents for 3095FT
Page 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Page 2: ......
Page 4: ......
Page 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Page 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Page 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Page 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Page 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Page 149: ...A 3 Appendix A...
Page 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Page 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Page 153: ...B 3 Appendix B...
Page 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Page 155: ...B 5 Appendix B...
Page 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Page 157: ...B 7 Appendix B...
Page 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Page 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Page 161: ...C 3 Appendix C...
Page 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Page 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Page 165: ...D 3 Appendix D...
Page 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Page 167: ...D 5 Appendix D...
Page 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Page 183: ......