4. Input modules
4−38
Festo P.BE−CPX−EA−EN en 0705f
Status LEDs
There is a green status LED for each input. This LED indicates
the status of the signal at the relevant input. This means:
Status LED
(green)
Sequence
Status
LED lights up
ON
OFF
logical 1 (signal present)
LED is out
ON
OFF
logical 0 (no signal)
Tab.4/34:
Status LED of the input modules
Fault LED
The red fault LED indicates a module fault due to short circuit
or overload of the sensor supply depending on the para
meterization.
Fault LED
(red)
Sequence
Status
Fault
number
Fault
treatment
LED is out
ON
OFF
Faultless operation
0
none
LED lights up
ON
OFF
Fault short circuit/overload
Short circuit/overload in sensor
supply (V
EL/SEN
).
2
See section
4.5.1, Tab.4/33
Tab.4/35:
Fault LED of the input modules