The following examples show the different address as-
signments and the position of the low byte (n) and the
high byte (n+1). A distinction is made here between the:
– Siemens mode and the
– Standard mode
Example:
– In the Siemens mode the lower value output byte
(byte n) is mapped on valve coils 0-7 of the valve
terminal, byte n+1 is mapped on coils (8-15), etc.
– In the Standard mode the lower value output byte
(byte n) is mapped on valve coils 8-15 of the valve
terminal, byte n+1 is mapped on coils 0-7.
In the following chapters you will find instructions on
modifying the position of the low bytes and high bytes
("Byte swap").
– with hardware by means of the DIL switch setting
(chapter 2.4.2, "Manufacturer-specific addressing by
means of the DIL switch")
– with software in a user-friendly manner by re-addres-
sing with the CMD software (chapter 2.4.3 "Process
data assignment by means of CMD software”). The
DIL switch setting remains unchanged (factory set-
ting).
2. Commissioning
2-20
CP FB6-E 9809c