Set the following functions on the DIL switch:
Dual in-line
switch
– Switch the automatic valve test on/off
– Select the common error messages/periphery
messages
– Manufacturer-specific addressing
(byte swap) on the INTERBUS
DIL switch
(factory
setting)
Switch
Function description
1
Valve test
ON:
CP system start without valve test
OFF: CP system start with valve test
(operation see chapter 3.2)
2
Select common error messages/
periphery messages
OFF: all error messages are transmitted
ON:
only error messages 3, 4, 5 are
transmitted (see chapter 3.3.2)
3
ON:
must be set at ON
OFF: reserved for internal test purposes
4
Manufacturer-specific addressing
(byte swap):
OFF: "Siemens mode"
ON:
"Standard mode" (other controllers)
1
2
3
4
ON
1. Installation
CP FB6-E 9809c
1-5