5-4
(F codes continued)
Code Name
Data
setting
range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
F18
Bias
(Frequency command 1)
-100.00 to 100.00 *2
0.01
%
Y*
Y
0.00
5-36
F20
DC Braking 1
(Braking starting
frequency)
0.0 to 60.0
0.1
Hz
Y
Y
0.0
5-37
F21
(Braking level) 0 to 100
1
%
Y
Y
0
F22
(Braking time) 0.00 (Disable), 0.01 to 30.00
0.01
s
Y
Y
0.00
F23
Starting Frequency 1
0.1 to 60.0
0.1
Hz
Y
Y
1.0
5-38
F24
(Holding time) 0.00 to 10.00
0.01
s
Y
Y
0.00
F25
Stop Frequency
0.1 to 60.0
0.1
Hz
Y
Y
0.2
F26
Motor Sound
(Carrier frequency)
0.75 to 16
1
kHz
Y
Y
ACU:2
E:15
5-39
F27
(Tone) 0: Level 0 (Inactive)
–
–
Y
Y
0
1:
Level
1
2:
Level
2
3:
Level
3
F30
Analog Output [FMA]
(Voltage adjustment)
0 to 300
1
%
Y*
Y
100
5-40
F31 (Function)
Select a function to be monitored from the
followings.
– –
Y Y 0
0: Output frequency 1 (before slip
compensation)
1: Output frequency 2 (after slip
compensation)
2:
Output
current
3:
Output
voltage
6:
Input
power
7: PID feedback amount (PV)
9: DC link bus voltage
14:
Calibration
15: PID command (SV)
16:
PID
output
(MV)
F37
0: Variable torque load
–
–
N
Y
1
5-26
1: Constant torque load
2:
Auto-torque
boost
3: Auto-energy saving operation (Variable
torque load during ACC/DEC)
4: Auto-energy saving operation (Constant
torque load during ACC/DEC)
Load Selection/Auto
Torque Boost/
Auto Energy Saving
Operation 1
5: Auto-energy saving operation
(Auto-torque boost during ACC/DEC)
F39
Stop Frequency
0.00 to 10.00
0.01
s
Y
Y
0.00
5-38
(Holding
Time)
F42
Control Mode Selection
1
0: V/f control with slip compensation
inactive
– –
N Y 0 5-41
1: Dynamic torque vector control
2: V/f control with slip compensation active
11: V/f control for PMSM drive *1
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).
*1 Available in the ROM version 0500 or later.
*2 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.