Example of Thermal Overload Detection Characteristics
F14
H13
H14
Restart Mode after Momentary Power Failure
Restart Mode after Momentary Power Failure, Restart time
Restart Mode after Momentary Power Failure, Frequency fall rate
F14 specifies the action to be taken by the inverter such as trip and restart in the event of a
momentary power failure.
Restart mode after momentary power failure (Mode selection) (F14)
Data for F14
Mode Description
0 Disable
restart
(Trip immediately)
As soon as the DC link bus voltage drops below the
undervoltage detection level due to a momentary power
failure, the inverter issues undervoltage alarm
lu
and
shuts down its output so that the motor enters a
coast-to-stop state.
1 Disable
restart
(Trip after recovery
from power failure)
As soon as the DC link bus voltage drops below the
undervoltage detection level due to a momentary power
failure, the inverter shuts down its output so that the
motor enters a coast-to-stop state, but it does not enter
the undervoltage state or issue undervoltage alarm
lu
.
The moment the power is restored, an undervoltage
alarm
lu
is issued, while the motor remains in a
coast-to-stop state.