5-63
P99
Motor 1 Selection
P99 specifies the type of motor 1 to be used.
Data for P99
Motor type
0
Motor characteristics 0 (Fuji standard IM, 8-series)
1
Motor characteristics 1 (HP rating IM. Typical in North America)
3
Motor characteristics 3 (Fuji standard IM, 6-series)
4
Other motors (IM)
20
Other motors (PMSM)
21
Fuji standard PMSM without sensor (GNB series)
Automatic control (such as auto torque boost and auto energy saving) or electronic thermal
overload protection for motor uses the motor parameters and characteristics. To match the
property of a control system with that of the motor, select characteristics of the motor and set
H03 data (Data Initialization) to "2" to initialize the motor parameters stored in the inverter. The
initialization automatically updates the P03 and P06 to P12 data and the constants used
inside the inverter.
According to the motor model, set the P99 data as shown below.
• For Fuji standard IM, 8-series (Current standard induction motors), P99 = 0
• For Fuji standard IM, 6-series (Conventional standard induction motors), P99 = 3
• For other manufacturers' IM or model-unknown IM, P99 =4
• For PMSM, P99 = 20 or 21 (to be selected after consultation with motor manufacturers)
• When P99 = 4, the inverter runs following the motor characteristics of Fuji
standard IM, 8-series.
• When P99 = 1, the inverter applies to the characteristics of HP rating IM (Typical
in North America).