6-1
Chapter 6 TROUBLESHOOTING
6.1 Before
Proceeding
with
Troubleshooting
If any of the protective functions has been activated, first remove the cause. Then, after checking
that the all run commands are set to OFF, reset the alarm. If the alarm is released while any run
command is set to ON, the inverter may supply the power to the motor, running the motor.
Injury may occur.
- Even though the inverter has interrupted power to the motor, if the voltage is applied to the
main circuit power input terminals L1/R, L2/S and L3/T (L1/L and L2/N for single-phase
voltage input), voltage may be output to inverter output terminals U, V, and W.
- Turn OFF the power and wait at least five minutes. Make sure that the LED monitor is turned
OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus
voltage between the terminals P (+) and N (-) has dropped to the safe level (+25 VDC or
below).
Electric shock may occur.
Follow the procedure below to solve problems.
(1) First, check that the inverter is correctly wired, referring to Chapter 2 Section 2.3.5 "Wiring for
main circuit terminals and grounding terminals."
(2) Check whether an alarm code is displayed on the LED monitor.
If any problems persist after the above recovery procedure, contact your Fuji Electric representative.