2.3.2 Terminal arrangement and screw specifications
The figures below show the arrangement of the main and control circuit terminals which differs
according to inverter type. The two terminals prepared for grounding, which are indicated by the
symbol
G in Figures A to D, make no distinction between the power supply side (primary circuit)
and the motor side (secondary circuit).
(1) Arrangement of the main circuit terminals
Table 2.3 Main Circuit Terminals
Power
supply
voltage
Nominal ap-
plied motor
(kW)
Inverter type
Terminal
screw size
Tightening
torque
(N·m)
Refer to:
0.1 FRN0001C2S-2
0.2 FRN0002C2S-2
0.4 FRN0004C2S-2
0.75 FRN0006C2S-2
M3.5 1.2
Figure
A
1.5 FRN0010C2S-2
2.2 FRN0012C2S-2
Three-
phase
200 V
3.7 FRN0020C2S-2
0.4 FRN0002C2S-4
0.75 FRN0004C2S-4
1.5 FRN0005C2S-4
2.2 FRN0007C2S-4
Three-
phase
400 V
3.7
(4.0)*
FRN0011C2S-4
M4 1.8
Figure
B
0.1 FRN0001C2S-7
0.2 FRN0002C2S-7
0.4 FRN0004C2S-7
0.75 FRN0006C2S-7
M3.5 1.2
Figure
C
1.5 FRN0010C2S-7
Single-
phase
200 V
2.2 FRN0012C2S-7
M4 1.8
Figure
D
Note: A box (
) in the above table replaces A, C, E, or U depending on the shipping destination. For
three-phase 200 V class series of inverters, it replaces A or U.
* 4.0 kW for the EU. The inverter type is FRN0011C2S-4E.