![FE FRENIC-Mini Instruction Manual Download Page 121](http://html.mh-extra.com/html/fe/frenic-mini/frenic-mini_instruction-manual_547580121.webp)
5-44
Compact models
When using the compact models of braking resistor TK80W120
Ω
or TK80W100
Ω
, set F50 to
"7" and F51 to "0.033."
10% ED models
Braking resistor
Continuous braking
(100% braking torque)
Intermittent braking
(Period: 100 s or less)
Power
supply
voltage
Inverter type
Type Qty.
Resistance
(
Ω
)
Discharging
capacity
(kWs)
Braking
time
(s)
Allowable
average
loss (kW)
Duty
(%ED)
FRN0004C2S-2
250
37
FRN0006C2S-2
DB0.75-2C
100 50
133
0.075
20
FRN0010C2S-2
73
14
FRN0012C2S-2
DB2.2-2C 40
55
50
0.110
Three-
phase
200 V
FRN0020C2S-2
DB3.7-2C
33
140
75
0.185
10
FRN0002C2S-4
250
37
FRN0004C2S-4
DB0.75-4C
200 50
133
0.075
20
FRN0005C2S-4
73
14
FRN0007C2S-4
DB2.2-4C 160
55
50
0.110
Three-
phase
400 V
FRN0011C2S-4
DB3.7-4C
130
140
75
0.185
10
FRN0004C2S-7
250
37
FRN0006C2S-7
DB0.75-2C
100 50
133
0.075
20
FRN0010C2S-7
73
14
Single-
phase
200 V
FRN0012C2S-7
DB2.2-2C
1
40 55
50
0.110
10
Note: A box (
) in the above table replaces A, C, E, or U depending on the shipping destination. For
three-phase 200 V class series of inverters, it replaces A or U.
E01 to E03,
E98, E99
Terminal [X1] to [X3] Function
Terminal [FWD] and [REV] Function
Function codes E01 to E03, E98 and E99 allow you to assign commands to terminals [X1] to
[X3], [FWD], and [REV] which are general-purpose, programmable, digital input terminals.
These function codes may also switch the logic system between normal and negative to
define how the inverter logic interprets either ON or OFF status of each terminal. The default
setting is normal logic system "Active ON." So, explanations that follow are given in normal
logic system "Active ON."
In the case of digital input, you can assign commands to the switching means for the run
command and its operation and the reference frequency (e.g.,
SS1
,
SS2
,
SS4
,
SS8
,
Hz2/Hz1
,
Hz/PID
,
IVS
, and
LE
). Be aware that switching any of such signals may cause a sudden start
(running) or an abrupt change in speed.
An accident or physical injury may result.