8-1
Chapter 8 SPECIFICATIONS
8.1 Standard
Models
8.1.1 Three-phase 200 V class series (
= A, U)
Item Specifications
Type (FRN_ _ _ _ C2S-2
) 0001 0002 0004 0006 0010 0012 0020
Applicable motor rating (kW)
*1
(when
= A)
0.1 0.2 0.4 0.75 1.5 2.2 3.7
Applicable motor rating (HP)
*1
(when
= U)
1/8 1/4 1/2 1 2 3 5
Rated capacity (kVA)
*2
0.30 0.57 1.3 2.0 3.5 4.5 7.2
Rated voltage (V)
*3
Three-phase, 200 to 240 V (with AVR function)
Rated current (A)
*4
0.8
(0.7)
1.5
(1.4)
3.5
(2.5)
5.5
(4.2)
9.2
(7.0)
12.0
(10.0)
19.1
(16.5)
Overload capability
150% of rated output current for 1 min.
150% of rated output current for 1 min or 200% of rated output current
for 0.5 s (for the rated current given in parentheses)
Output Rating
s
Rated frequency (Hz)
50/60 Hz
Phases, voltage,
frequency
Three-phase, 200 to 240 V, 50/60 Hz
Voltage and
frequency variations
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*5
,
Frequency: +5 to -5%
(w/
DCR)
0.57 0.93 1.6 3.0 5.7 8.3 14.0
Rated
current (A)
*6
(w/o
DCR)
1.1 1.8 3.1 5.3 9.5 13.2
22.2
Input Ra
tings
Required power
supply capacity (kVA)
*7
0.2 0.3 0.6 1.1 2.0 2.9 4.9
Torque (%)
*8
150
100
50
30
DC braking
Braking starting frequency
*9
: 0.0 to 60.0 Hz,
Braking time: 0.0 to 30.0 s, Braking level: 0 to 100%
Braking
Braking transistor
--
Built-in
Applicable safety standards
UL508C, IEC 61800-5-1: 2007 (under application)
Enclosure
IP20 (IEC 60529:1989), UL open type (UL50)
Cooling method
Natural cooling
Fan cooling
Mass
(kg)
0.6 0.6 0.7 0.8 1.7 1.7 2.5
*1 Fuji 4-pole standard motors
*2 Refers to the rated capacity assuming the rated output voltage as 220 V.
*3 Output voltages cannot exceed the power supply voltage.
*4 The load shall be reduced so that the continuous operating current is the rated current in parentheses or less if
the carrier frequency is set to 3 kHz or above or the ambient temperature exceeds 40°C.
*5
2004)
:
3
-
61800
IEC
to
(Refer
67
(V)
voltage
average
phase
-
3
(V)
e
Min.voltag
-
(V)
voltage
Max.
(%)
unbalance
voltage
Interphase
×
=
If this value is 2 to 3%, use an optional AC reactor (ACR).
*6 Refers to the estimated value to apply when the power supply capacity is 500 kVA (inverter capacity x 10 when
the inverter capacity exceeds 50 kVA) and the inverter is connected to the %X = 5% power supply.
*7 Refers to the value to apply when a DC reactor (DCR) is used.
*8 Refers to the average braking torque to apply when the motor running alone decelerates from 60 Hz with the
AVR control being OFF. (It varies with the efficiency of the motor.)
*9 Available only for induction motor drive.
Note: A box (
) in the above table replaces A or U depending on the shipping destination.