5-45
Function code data
Active ON
Active OFF
Terminal commands assigned
Symbol
0 1000
SS1
1 1001
SS2
2 1002
SS4
3 1003
Select multistep frequency (0 to 15 steps)
SS8
4 1004
Select
ACC/DEC
time
RT1
6
1006
Enable 3-wire operation
HLD
7
1007
Coast to a stop
BX
8 1008
Reset
alarm
RST
1009
9
Enable external alarm trip
THR
10
1010
Ready for jogging
JOG
11
1011
Select frequency command 2/1
Hz2/Hz1
12
1012
Select motor 2 / motor 1
M2/M1
13
⎯
Enable DC braking
DCBRK
17
1017
UP (Increase output frequency)
UP
18
1018
DOWN (Decrease output frequency)
DOWN
19
1019
Enable data change with keypad
WE-KP
20 1020
Cancel
PID
control
Hz/PID
21 1021
Switch
normal/inverse
operation
IVS
24
1024
Enable communications link via RS-485
LE
33
1033
Reset PID integral and differential components
PID-RST
34
1034
Hold PID integral component
PID-HLD
98
⎯
Run forward
(Exclusively assigned to [FWD] and [REV] terminals
by E98 and E99)
FWD
99
⎯
Run reverse
(Exclusively assigned to [FWD] and [REV] terminals
by E98 and E99)
REV
Any negative logic (Active OFF) command cannot be assigned to the functions
marked with "
⎯
" in the "Active OFF" column.
The "Enable external alarm trip" and "Force to stop" are fail-safe terminal
commands. For example, when data = 9 in "Enable external alarm trip," "Active
OFF" (alarm is triggered when OFF); when data = 1009, "Active ON" (alarm is
triggered when ON).