9-1
Chapter 9 LIST OF PERIPHERAL EQUIPMENT AND OPTIONS
The table below lists the main peripheral equipment and options that are connected to the
FRENIC-Mini. Use them in accordance with your system requirements.
For details, refer to the FRENIC-Mini User's Manual (24A7-E-0023), Chapter 6 "SELECTING
PERIPHERAL EQUIPMENT."
Name of
peripheral
equipment
Function and application
Main peripheral e
quipment
Molded case
circuit breaker
(MCCB)
Residual-current-
operated
protective device
(RCD)
/Earth leakage
circuit breaker
(ELCB)*
*
with overcurrent
protection
MCCBs are designed to protect the power circuits between the power control
board and inverter’s main terminals (L1/R, L2/S and L3/T for three-phase
power, L1/L and L2/N for single-phase power) from overload or short-circuit
which in turn prevents secondary disasters caused by the inverter
malfunctioning.
RCDs/ELCBs function in the same way as MCCBs. Use the MCCBs and
RCDs/ELCBs that satisfy the recommended rated current listed below.
Recommended rated current (A) of
MCCB and RCD/ELCB
Power
supply
voltage
Applicable
motor
rating
(kW)
Inverter type
w/ DC reactor
w/o DC reactor
0.1 FRN0001C2S-2
0.2 FRN0002C2S-2
0.4 FRN0004C2S-2
5
0.75 FRN0006C2S-2
5
10
1.5 FRN0010C2S-2
15
2.2 FRN0012C2S-2
10
20
Three-
phase
200 V
3.7 FRN0020C2S-2
20 30
0.4 FRN0002C2S-4
0.75 FRN0004C2S-4
5
1.5 FRN0005C2S-4
10
2.2 FRN0007C2S-4
5
15
Three-
phase
400 V
3.7
(4.0)*
FRN0011C2S-4
10
20
0.1 FRN0001C2S-7
0.2 FRN0002C2S-7
5
0.4 FRN0004C2S-7
5
10
0.75 FRN0006C2S-7
10 15
1.5 FRN0010C2S-7
15 20
Single-
phase
200 V
2.2 FRN0012C2S-7
20 30
Note: A box (
) in the above table replaces A, C, E, or U depending on the
shipping destination. For three-phase 200 V class series of inverters, it
replaces A or U.
* 4.0 kW for the EU. The inverter type is FRN0011C2S-4E.