8-4
8.2 Common
Specifications
Item Explanation
Maximum
frequency
25.0 to 400.0 Hz variable
Base frequency
25.0 to 400.0 Hz variable
Starting frequency
0.1 to 60.0 Hz variable
Setting range
Carrier frequency
0.75 to 16 kHz variable
Note:
To protect the inverter, when the carrier frequency is 6 kHz or
more, the carrier frequency automatically lowers depending upon
the ambient temperature or output current states. (The automatic
lowering function can be disabled.)
*1
Output frequency
accuracy (Stability)
• Analog setting: ±2% of max freq. (at 25°C), temperature drift:
±0.2% of max freq. (at 25±10°C)
• Keypad setting: ±0.01% of max freq. (at 25°C), temperature drift:
±0.01% of max freq. (at 25±10°C)
Output frequenc
y
Frequency setting
resolution
• Analog setting: 1/1000 of maximum frequency
• Keypad setting: 0.01 Hz (99.99 Hz or less), 0.1 Hz (100.0 to 400.0
Hz)
• Link setting:
1/20000 of maximum frequency or 0.01 Hz (fixed)
Control system
Driving induction motor (IM)
• V/f control, slip compensation, auto torque boost
• Dynamic torque vector control, automatic energy saving control
Driving permanent magnet synchronous motor (PMSM) (without
speed / position sensor)
*2
• Speed control range: 10% or more of the base frequency
200 V
series
• Possible to set output voltage at base frequency and
at maximum output frequency (80 to 240 V).
• The AVR control
*1
can be turned ON or OFF.
• Non-linear V/f
*1
setting (2 points): Free voltage (0 to
240 V) and frequency (0 to 400 Hz) can be set.
Voltage/frequency
characteristics
400 V
series
• Possible to set output voltage at base frequency and
at maximum output frequency (160 to 500 V).
• The AVR control
*1
can be turned ON or OFF.
• Non-linear V/f
*1
setting (2 points): Free voltage (0 to
500 V) and frequency (0 to 400 Hz) can be set.
Torque boost
*1
• Auto torque boost (For constant torque load)
• Manual torque boost: Torque boost value can be set between 0.0
and 20.0%.
• Select application load with the function code. (For variable torque
load or constant torque load)
Starting torque
*1
• 150% or more (Running at 1 Hz, with slip compensation and auto
torque boost active)
Keypad: Start and stop with RUN and STOP keys (standard keypad/
optional remote keypad)
External signals (digital inputs): Run forward and stop command,
Run reverse and stop command, coast-to-stop command, etc.
Control
Start/stop operation
Link operation: Operation through RS-485 (built-in as standard)
*
1 Available only for induction motor drive.
*2 Available in the ROM version 0500 or later.