5-49
Select motor 2 / motor 1 --
M2
/
M1
(Function code data = 12)
Turning this terminal command ON switches from motor 1 to motor 2. Switching is possible
only when the inverter is stopped. Upon completion of switching, the digital terminal output
"Switched to motor 2"
SWM2
(assigned to any of terminals [Y1] and [30A/B/C]) turns ON.
If no
M2/M1
terminal command is assigned, motor 1 is selected by default.
Input terminal command
M2
/
M1
Selected motor
SWM2
status
after completion of switching
OFF Motor
1
OFF
ON Motor
2
ON
Switching between motors 1 and 2 automatically switches applicable function codes as listed
below. The inverter runs the motor with those codes that should be properly configured.
Function code name
For Motor 1
For Motor 2
Maximum Frequency
F03
A01
Base Frequency
F04
A02
Rated voltage at Base Frequency
F05
A03
Maximum Output Voltage
F06
A04
Torque Boost
F09
A05
Electronic Thermal Overload Protection for Motor
(Select motor characteristics)
F10 A06
(Overload detection level)
F11
A07
(Thermal
time
constant)
F12
A08
DC Braking
(Braking starting frequency)
F20
A09
(Braking
level)
F21
A10
(Braking
time)
F22
A11
Starting Frequency
F23
A12
Load Selection/Auto Torque Boost/Auto Energy Saving Operation
F37
A13
Control Mode Selection
F42
A14
Motor Parameters
(No. of poles)
P02
A16
(Rated
current)
P03
A17
(Auto-tuning) P04
A18
(No-load
current)
P06
A20
(%R1)
P07
A21
(%X)
P08
A22
(Slip compensation gain for driving)
P09
A23
(Slip compensation response time)
P10
A24
(Slip compensation gain for braking)
P11
A25
(Rated slip frequency)
P12
A26
Motor Selection
P99
A39
Output Current Fluctuation Damping Gain for Motor
H80
A41
Cumulative Motor Run Time
H94
A51
Startup Counter of Motor
H44
A52