Setting the PID process command with the built-in potentiometer
(1) Set function code E60 to "3: PID process command 1."
(2) Set function code J02 to "1: PID process command 1."
Setting the PID process command with the
and
keys
(1) Set function code J02 to "0:
/
keys on the built-in keypad."
(2) Set the LED monitor to an item other than the speed monitor (E43 = 0) in Running mode. In
Programming mode or Alarm mode, the
/
keys cannot be used for setting the PID
process command, so switch to Running mode.
(3) Press
the or
key to display the PID process command. The lowest digit of the displayed
command and the decimal point blink.
(4) To change the PID process command, press the
or
key again. The new PID process
command will be automatically saved into the inverter’s memory. It is kept there even if the
inverter is switched to any other PID process command entry method and then returned to the
keypad entry method. Also, it is kept there even if the inverter is powered off, and it will be used
as the initial PID process command next time the inverter is powered on.
• Even if multistep frequency is selected as a PID process command (
SS4
= ON), you still
can set the process command using the keypad.
• When function code J02 data has been set to any value except "0," pressing the
or
key displays the currently selected PID process command but does not allow any
change of the setting.
• When a PID process command is displayed, the decimal point next to the lowest digit on
the LED display blinks to distinguish it from the regular frequency setting. When a PID
feedback amount is displayed, the decimal point is lit.