Conformity to the Low Voltage Directive in the EU (Continued)
12. Use wires listed in IEC60364-5-52.
MCCB: Molded case circuit breaker
RCD: Residual-current-operated protective device
ELCB: Earth leakage circuit breaker
Note: A box (
) in the above table replaces A, C, E, or U depending on the shipping destination. For
three-phase 200 V class series of inverters, it replaces A or U.
* 4.0 kW for the EU. The inverter type is FRN0011C2S-4E.
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary,
depending on the power transformer capacity. Refer to the related technical documentation for
details.
*2 The recommended wire size for main circuits is for the 70
°
C 600V PVC wires used at an ambient
temperature of 40
°
C.
*3 In the case of no DC reactor, the wire sizes are determined on the basis of the effective input
current calculated under the condition that the power supply capacity and impedance are 500 kVA
and 5%, respectively.
Recommended wire size (mm
2
)
*1
Rated current (A)
of
MCCB or RCD/ELCB
*2
Main circuit
power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Grounding [
G]
Power su
pply v
oltag
e
Appli-
cable
motor
rating
(kW)
Inverter type
w/ DCR
*3
w/o DCR
w/ DCR
*3
w/o DCR
*2
Inverter
output
[U, V,
W]
*2
DCR
[P1,
P (+)]
Braking
resistor
[P (+),
DB]
Control
circuit
(30A,
30B,
30C)
0.1 FRN0001C2S-2
□
0.2 FRN0002C2S-2
□
0.4 FRN0004C2S-2
□
6
0.75 FRN0006C2S-2
□
6
10
1.5 FRN0010C2S-2
□
16
2.2 FRN0012C2S-2
□
10
20
2.5 2.5
Three-ph
ase 2
00 V
3.7 FRN0020C2S-2
□
20
35
2.5
4 4
2.5 0.5
0.4 FRN0002C2S-4
□
0.75 FRN0004C2S-4
□
6
1.5 FRN0005C2S-4
□
6
10
2.2 FRN0007C2S-4
□
16
Three-ph
ase 4
00 V
3.7
(4.0)*
FRN0011C2S-4
□
10
20
2.5 2.5 2.5
2.5 0.5
0.1 FRN0001C2S-7
□
0.2 FRN0002C2S-7
□
6
0.4 FRN0004C2S-7
□
6
10
0.75 FRN0006C2S-7
□
10
16
2.5
1.5 FRN0010C2S-7
□
16
20
2.5
4
2.5
Single-p
hase 200
V
2.2 FRN0012C2S-7
□
20
35
4
6
2.5
4
0.5