Appendix A – Central Station Reporting Formats
A–3
restore, etc.) to a specific zone (e.g., up to 8 zones in the XL-1T system), and to report
openings/closings for many users (e.g., up to 15 users in the XL-1T system).
For some report codes, the first of the two programmable digits determines the PID Event
Code to be transmitted. Other reporting codes transmit a dedicated PID Event Code
regardless of the digit programmed in the first location. In both cases, if transmissions are
not desired, then program AA in locations 1 and 2. Refer to the tables that follow to select
the PID Event Codes to be transmitted.
BURGLARY ZONE TYPES
FIRE ZONE TYPES
Digit
EVENT
CODE
ENGLISH OUTPUT AT
CS RECEIVER
Digit
EVENT
CODE
ENGLISH OUTPUT AT
CS RECEIVER
0
122
Silent Panic
0
110
Fire Alarm
1
123
Audible Panic
1
111
Smoke
2
130
Burglary
2
112
Combustion
3
131
Perimeter
3
113
Water Flow
4
132
Interior
4
114
Heat
5
133
24 Hour Alarm
5
115
Pull Station
6
134
Entry/Exit
6
116
Duct
7
135
Day/Night
7
117
Flame
8
136
Outdoor
8
140
General Alarm
9
137
Tamper
9
150
24 Hour Non-Burg
A
140
General Alarm
A
158
High Temperature
B
144
Sensor Tamper
B
159
Low Temperature
C
155
Foil Break
C
200
Fire Supervisory
D
156
Day Trouble
D
201
Low H
2
O Pressure
E
202
Low CO
2
F
203
Gate Valve Sensor
Summary of Contents for XL-1T
Page 2: ...ii ...
Page 10: ...XL 1T Installation and Setup Guide 1 2 ...
Page 26: ...XL 1T Installation and Setup Guide 4 4 ...
Page 32: ...XL 1T Installation and Setup Guide 5 6 ...
Page 36: ...XL 1T Installation and Setup Guide 6 4 ...
Page 58: ...XL 1T Installation and Setup Guide 8 4 ...
Page 60: ...XL 1T Installation and Setup Guide 9 2 ...
Page 66: ...XL 1T Installation and Setup Guide B 2 ...
Page 72: ... 1 6l N9883 09 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset NY 11791 ...