Section 7 - System Programming
7–13
Burglary Zone Options
RESTORE - This option is selected for all burglary zones by enabling the Restore Report
Code (question 19, location 2), and enabling transmit zone restores in question #07, location
2. The programmed Restore Code will be reported upon bell cutoff. The Restore Code will
also be reported if the system is disarmed during an alarm.
Restore is not selectable by zone.
BYPASS IN STAY - This option allows zones to be bypassed when the system is armed in
the STAY mode.
CHIME - If this option is selected, the keypad sounder will annunciate for 1 second when the
zone is violated in the disarmed mode.
DIALER DELAY - If this option is selected for a Burglary zone (quest. #07, location 2), the
system will allow a 15-second delay before dialing allowing the end user to ABORT the
transmission. If this option is not selected, any alarm condition will result in an immediate
transmission that cannot be aborted.
UL
For UL installations, dialer delay may not be used.
DAY FEATURE - If a zone with this option is violated while the system is disarmed, the
keypad sounder and zone LED will pulse for as long as the violation remains, and the panel
will dial the central station 15 seconds after the violation of the zone. In addition, the System
Trouble Code will be transmitted to the central station. The sounder can be silenced by
entering a valid User Code. While the system is armed, a DAY zone will act as an alarm
when violated.
FAST ZONE - If enabled, the zone response will be 10mSec. If not selected, it will be
280mSec.
24 Hour Zones
Zones 1-4 can be programmed for any one of the following 24-hour zone types:
24 HOUR ZONES
ZONE TYPE
ZONE OPTIONS
L1L2
Digits
24 HR.
ALARM
FIRE
24 HR.
TROUBLE
AUDIBLE
SILENT
81
9
9
82
9
9
84
9
ALWAYS AUDIBLE
89
9
9
8A
9
9
FIRE - Fire zones on the system contain Fire Verification Logic. Upon detection of the first
violation, smoke detector power will be reset for a period of eight seconds. After this time
period, power is restored. For a period of five seconds, the fire zone will not be scanned
allowing the smoke detectors to settle. Future violations, within a two-minute period, will
result in a pulsing bell output, rapid pulsing zone LED, and immediate transmission to the
CS. Please note, fire signals cannot be aborted.
Summary of Contents for XL-1T
Page 2: ...ii ...
Page 10: ...XL 1T Installation and Setup Guide 1 2 ...
Page 26: ...XL 1T Installation and Setup Guide 4 4 ...
Page 32: ...XL 1T Installation and Setup Guide 5 6 ...
Page 36: ...XL 1T Installation and Setup Guide 6 4 ...
Page 58: ...XL 1T Installation and Setup Guide 8 4 ...
Page 60: ...XL 1T Installation and Setup Guide 9 2 ...
Page 66: ...XL 1T Installation and Setup Guide B 2 ...
Page 72: ... 1 6l N9883 09 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset NY 11791 ...