3–1
WARNING
: To prevent risk from
electrical shock, de-energize the
system control unit and disconnect
the telephone lines before servicing
this unit.
CONTROL PANEL
POWER
DETAIL A
12
13
1
2
3
4
ZONE
SMOKE DETECTOR
9.5 - 12.2VDC
LISTED
HOUSEHOLD
THERMOSTAT
ESL 104
MODEL ESL2048
EOL RELAY
RED
BLACK
BROWN
BROWN
2.2k EOL RESISTOR
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
UL INSTALLATIONS REQUIRE LISTED
END-OF-LINE DEVICE. USE RESISTOR
FROM EOL22 KIT. LOOK FOR LISTING
MARK ON ITEM.
WARNING:
THIS UNIT INCLUDES AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNIT
PLUS SMOKE DETECTOR) SHALL NOT EXCEED
60 SECONDS. NO OTHER INITIATING DEVICES
SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
CIRCUIT CONTROL UNIT SMOKE DETECTOR
(ZONE) DELAY-SEC MODEL DELAY-SEC
_______ _____20______ ______ __________
PRODUCT COVERED UNDER
US PATENT #4,791,658
XL-1T
NOTES:
1. Connect to a grounded metal water pipe (16ga. at 15 ft.)
2. Total AUX. power available (including keypad power) is 500mA max.
(300mA max. for UL installations). Used for connection of devices rated
from 11.5 to 13.1VDC.
3. System must be tested on a weekly basis. For information, refer to manual.
4. Do not connect the transformer to a switch controlled receptacle.
Power varies with transformer (SEE NOTE 2).
5. Installation of equipment and wiring methods are required to be in accordance
with the National Electrical code and ANSI/NFPA No. 72.
6. Battery capacity for Emergency Standby is a minimum of 4 hours.
Under normal conditions this battery will last 3 years. Use only exact
replacements.
7. Maximum of 4 keypads. Available keypads include: XK-104 and 6805.
8. Limited energy cable must be used.
9. Non-replaceable fuse (F3). Return to manufacturer if blown. Do not solder in field.
10. Maximum for UL installations: Entry Delay, 45 sec.; Exit Delay, 60 sec.
11. For connection of VS-299 Siren Driver. Constant positive (+) unregulated output.
12. The PANIC or KEYSWITCH connected to terminals 5 & 7 is to be no more than 3 ft.
from the control unit with no barriers in between.
13. Programmable trigger outputs. If used for smoke detector power reset
see Detail A. See manual for programming information.
Use model XL-2GTC trigger cable.
SYSTEM DEFAULT RESET JUMPERS
TRANSFORMER
12VAC, 20VA
(Connect to 24 HR.
120VAC, 60 Hz Outlet
SEE NOTE 4)
+
-
SIREN
-
+
+
_
_
+
SMOKE
DETECTOR
POWER
(9.5-12.2VDC,
50mA max.)
BELL
22
16 17
18 19 20 21
9
10
11 12 13
14 15
CONSTANT DC POWER (+)
10-15.5VDC
(SEE NOTE 11)
KEYPAD
(SEE NOTE 7)
BLACK
YE
L
LOW
GREE
N
RED
FIRE & BURGLARY
ALARM OUTPUT
(11.5-13.1VDC,
1A max.)
HOME
TELCO
BROWN
GRAY
HOME
GREE
N
RED
TELCO
AUX POWER
12VDC Reg., 500mA max.
(SEE NOTE 2)
+
_
PANIC
2.2K
2.2K
4
3
2
1
EARTH GND.
(SEE NOTE 1)
5
6
7
8
2.2K
2.2K
ZONE 1
ZONE 2
ZONE 3
ZONE 4
JP1
JP2
To re-load factory default values, remove all power
(AC & DC). Short JP1 to JP2. With short still applied,
re-apply power (AC then DC), wait 5 seconds, then
remove short with power still applied.
ZONE
1
2
3
4
PANIC
(+)
1
3
4
6
7
(-)
2
2
5
5
5
TERMINALS
CONNNECTIONS FOR HOUSEHOLD FIRE/BURGLAR ALARM SYSTEM
P1
VBE
L
L
T1
T2
+
BLACK
RED
12V, 4-6AH
BATTERY
MODEL 1240A
(SEE NOTE 6)
_
TRIGGER
OUTPUTS
(SEE NOTE 13)
Aux. Power
Bell Power
F3
Battery
4 Amps
This fuse is
NOT replaceable.
(SEE NOTE 9)
F1
F2
3 Amps
1 Amp
MODEL 368 CORD
TO RJ31X OR
CA31A JACK
FCC Registration Number AE398E-69554 AL-E Ringer Equivalence 0.0B
References: Hookup and Installation Instructions N9983 and Owner’s Manual N9884
LOAD NO.: 7
S E C T I O N 3
System Wiring and Hookup
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
System Wiring Diagram
Figure 3-1: Summary of Connections
SYSTEM STABILIZATION MODE: Upon initial power-up of the system, all of the lights on the LED
keypad(s) will blink ON and go OFF for approximately 2 min. 10 seconds; and/or the LCD keypad(s) will
display STAND BY! for approximately 2 min. 10 seconds. This occurs on a total power-up (if armed or
disarmed in its prior state) or after a system reset. If the total system power is lost upon power
restoration, the system will return to the previous arming state. The 2 min. 10 sec. interval is used to
allow motion detectors (interior zones) to stabilize on power-up in order to prevent false alarms. This
option can be disabled by momentarily (5-second minimum) putting a jumper between terminals 13 and
12.
Summary of Contents for XL-1T
Page 2: ...ii ...
Page 10: ...XL 1T Installation and Setup Guide 1 2 ...
Page 26: ...XL 1T Installation and Setup Guide 4 4 ...
Page 32: ...XL 1T Installation and Setup Guide 5 6 ...
Page 36: ...XL 1T Installation and Setup Guide 6 4 ...
Page 58: ...XL 1T Installation and Setup Guide 8 4 ...
Page 60: ...XL 1T Installation and Setup Guide 9 2 ...
Page 66: ...XL 1T Installation and Setup Guide B 2 ...
Page 72: ... 1 6l N9883 09 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset NY 11791 ...