XL-1T Installation and Setup Guide
3–2
Terminal Connections
TERMINALS
DESCRIPTION
1(+) and 2(-)
Zone 1 (Requires 2.2K EOL resistor)
[Default = DELAY]
3(+) and 2(-)
Zone 2 (Requires 2.2K EOL resistor)
[Default = INTERIOR]
4(+) and 5(-)
Zone 3 (Requires 2.2K EOL resistor)
[Default = PERIMETER]
6(+) and 5(-)
Zone 4 (Requires 2.2K EOL resistor)
[Default = PERIMETER]
ZONE INFORMATION:
Normally closed devices may be wired in series and/or normally open
devices in parallel with the 2.2k ohm end-of-line resistor on all zones
(Refer to Figure 3-1: Summary of Connections). The standard loop
response time is 280mS on all zones. Each zone can be programmed for
Fast Response, 10mS (see questions #11-14). The factory default values
for each zone are listed in the table above; however; any zone can be
programmed for the following types: delay, perimeter, interior, fire, 24-hr.
alarm, or 24-hr. trouble. Further explanation of the zone types can be
found in Section 7: System Programming.
Loop response is defined as the minimum time required for a fault to trip a zone.
5 and 7
PANIC CIRCUIT OR KEYSWITCH:
This hardwired panic is a 24-hour zone that can be programmed for silent
or audible operation. The normally open panic circuit will activate with
each violation; therefore; a latched device is not recommended. A
momentary device is recommended. For UL installations, the panic
switch connected to these terminals should be located no more than three
feet from the control unit with no intervening barriers (this is a
supervision requirement only). If the Keyswitch option is selected (refer
to programming question #05, location 2), each activation of the
keyswitch will arm or disarm the system.
An EOL resistor is not required on this zone and is not supervised. This zone does not report
Restore Codes. If a supervised zone with restore reporting ability is desired, program one of the
four zones as a 24-hr. alarm. If the zone is used as a keyswitch, triggers are available for either an
arming or ready status indication (see programming question #07, location 4).
8
EARTH GROUND:
Connect this grounding lug to a cold water pipe utilizing #18AWG wire at
a distance of no greater than 15 ft. Use a noncorrosive metal strap firmly
secured to the pipe to which the lead is electrically connected and
secured. If the premises’ pipes terminate in PVC, this terminal must be
connected to a six-foot grounding rod.
Summary of Contents for XL-1T
Page 2: ...ii ...
Page 10: ...XL 1T Installation and Setup Guide 1 2 ...
Page 26: ...XL 1T Installation and Setup Guide 4 4 ...
Page 32: ...XL 1T Installation and Setup Guide 5 6 ...
Page 36: ...XL 1T Installation and Setup Guide 6 4 ...
Page 58: ...XL 1T Installation and Setup Guide 8 4 ...
Page 60: ...XL 1T Installation and Setup Guide 9 2 ...
Page 66: ...XL 1T Installation and Setup Guide B 2 ...
Page 72: ... 1 6l N9883 09 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset NY 11791 ...