UPS Transition Time
Transition time is the time that is necessary for the UPS to transfer from utility power to full-load battery
power. For Extreme Networks products, a transition time of less than 20 milliseconds is required for
optimum performance.
Applicable Industry Standards
For more information, see the following ANSI/TIA/EIA standards:
•
ANSI/TIA/EIA-568-A—discusses the six subsystems of a structured cabling system.
•
ANSI/TIA/EIA-569-A—discusses design considerations.
•
ANSI/TIA/EIA-606—discusses cabling system administration.
•
ANSI/TIA/EIA-607—discusses commercial building grounding and bonding requirements.
You can access these standards at:
www.ansi.org
or
www.tiaonline.org
.