ETEL Doc. - Operation & Software Manual # DSC2P 903 / Ver. F / 3/6/05
Chapter C: System functions
Operation & Software Manual
Direct Drives & Systems
203
13.11 Status Drive
The ’Status Drive’ are monitoring variables which enable the user to see if the controller is in error or warning
mode. Moreover, for an i
2
t error type, the integral value can be directly displayed via monitoring M67.
Monitorings
M60 (SD1)
,
M61 (SD2)
and
M63
enable the user to know if the initialization is over, if the motor is
moving, if the controller has detected an error... It is necessary to convert the value shown by monitorings M60,
M61 and M63 in binary. The three tables below show the meaning of each bit of monitorings M60, M61 and
M63. They are used for really advanced programming. Detailed explanations are not given in this manual.
13.11.1 M60 monitoring (SD1)
When a bit=1, its definition is validated
(the status description is verified). If a bit=0, its definition is not validated.
Example: Bit 0 = 1 means 'controller switched on' and bit 0 = 0 means 'controller switched off'.
The EXI command clears the bit# 9 of the SD1. So, it disables the editor mode of the sequence and builds label
table.
Example:
M60.1
;The ’Status Drive’ SD1 value is 2F; it means 101111 binary. It means that the power is on in
the motor, the phasing and homing have been completed and the position is kept 'in the window'
(bits 0, 1, 2, 3 and 5 are set to 1).
Available on
DSC2P
DSC2V
DSCDP
DSCDL
DSCDM
M
Alias
Name
Comment
M60
SD1
Status drive 1
Status drive (phasing, error, ...).
M61
SD2
Status drive 2
Status drive (process error label, ...).
M63
-
TEB status
TEB status
Available on
DSC2P
DSC2V
DSCDP
DSCDL
DSCDM
Bit #
Value
Bit definition (description when bit=1)
0
1
Controller in ’Power On’ mode
1
2
Phasing completed (first PWR.<axis> = 1)
2
4
First homing process completed
3
8
Motor (axis) present. Bit normally always set to 1.
4
16
Motor is executing a trajectory (moving)
5
32
Motor in the position/time window (In-window defined by parameters K38 and K39)
6
64
Controller in
µ
-master mode. This mode is set the controller is switched on when K170=1
7
128
Controller in waiting mode (commands WTM, WTP, WTW, WTB)
8
256
Controller executing an internal sequence (sequence in the controller)
9
512
Controller in edition
of sequence mode (EDI command). The writing of S sequences is allowed.
10
1024
Controller in error mode
11
2048
Trace busy flag is set during a register trace acquisition
13
8192
Homing process in progress
23
8388608
Controller global warning