12.12 Controller software characteristics
The following monitorings indicate useful data for the user (they cannot be modified).
Monitorings M71, M72 and M78:
Monitorings M72 and M78 contain, respectively, the firmware version numbers installed in the controller and in
an optional board if there is any. Monitoring M72 can directly be read with
VER
command (refer to
Monitoring M71 gives the software boot version of the controller.
The controller sends a firmware version, as a hexadecimal number, under the following form:
VER.1 = 0x
WWWXXYY
, with the following possible values:
For example, the hexadecimal value 0x
1208000
means that the firmware version 1.20A, released, is in the
controller.
Monitoring M90 shows the controller temperature in Celsius degrees. If the temperature inside the controller is
greater than 70°C (75°C for the DSCDM), the
OVER TEMPERAT
error (M64=5) will appear. If the thermostat
inside the controller is faulty (or if the power bridge of the DSC2V is overheating), the
SENSOR TEMP ERR
error (M64=13) will appear.
Available on
DSC2P
DSC2V
DSCDP
DSCDL
DSCDM
M
Alias
Name
Value
Comment
Units
M70
-
Controller type
6
7
8
10
DSC2P / DSC2V controller
DSCDP controller
DSCDL controller
DSCDM controller
-
M71
-
Controller boot software version
-
Number of the Boot software version installed in the controller (same
format as monitoring M72).
-
M72
VER
Controller firmware version
-
Number of the firmware version installed in the controller.
-
M73
SER
Controller serial number
-
Controller's serial number
-
M76
-
Optional board type
0
4
7
16
24
32
Optional board installed in the controller
(DSCDM)
No optional board in the controller
DSO-MAC: Macro field bus interface
(DSCDL)
DSO-HIO: Extension board with 8 digital I/O
DSO-CAN: CAN field bus interface, with CANetel protocol
(DSCDL)
DSO-SER: Sercos field bus interface
(Only on DSC2P and DSC2V)
DSO-PRO: Profibus field bus interface
(DSCDL)
-
M77
-
Optional board info boot revision
-
Number of the boot revision in the optional board
(DSCDM)
-
M78
-
Optional board firmware
-
Number of the firmware version installed in the optional board
(DSCDM)
-
M79
-
Optional board serial number
DSO-XXX board (installed in the controller) serial number
(DSCDM)
-
M85
-
Controller article number
-
Controller's article number (16 strings using 4 depths of M85)
-
M86
-
Optional board article number
-
DSO-XXX article number (16 strings using 4 depths of M86)
(DSCDL
and
DSCDM)
-
M87
-
Controller axis number
-
Controller's axis number
-
M90
-
Controller temperature
-
Controller's temperature (heat sink).
[°C]
M91
-
ContVpower measurement
-
Gives the DC bus Vpower level
(DSCDP
and
DSCDM)
Read M91: +Vpower[V] = M91 / 100
100·[V]
M92
-
Controller -Vpower measurement
Gives the negative DC bus Vpower level
(Only on DSCDL)
Read M92: -Vpower[V] = M92 / 100
M95
-
Controller display message
-
LCD display message (16 strings using 4 depths of monitoring M95)
-
M96
-
Sequence line
-
Number of line in the sequence currently processed by the controller
-
WWW: version # (3 digits)
XX: revision index (2 digits)
YY: status (2 digits)
Values examples
100
...
120
...
00
01
...
40
41
...
80
81
82
...
00
80
Meaning
1.00
...
1.20
...
α
0
α
1
...
ß
0
ß
1
...
A
B
C
...
released
in dev.