6 Commissioning
Mycom S CLM 153
58
EHauser
Points of the characteristic:
For
constant control gain
("linear characteristic"), you require:
Setpoint W,
Neutral zone
– Two-sided: "Start of the neutral zone" and "End of neutral zone"
– One-sided: only one of the two points
For
range-dependent modulation gain
("segmented characteristic"), you require two-
sided control of
all the points.
A point usually consists of two coordinates: an x coordinate (here = measured value)
and a y coordinate (here = actuating variable). You only need enter the y coordinates
for the optimisation points. For the other points, the CLM 153 sets the y coordinates
itself.
However, you cannot change the sequence of these defined points. It is, for example,
not possible to enter a larger measured value for the "Start neutral zone" than for the
setpoint.
Configuring the CLM 153
Please configure the relays in the following order:
1.
Actuators
2.
Sensor technology
3.
Feedback (e.g. look-ahead control, position feedback with three-point step
controller, if available)
4.
Characteristic:
In the user settings (seebelow) you switch directly to a controller simulation and can
check the settings made and change them if necessary.
To enter the menu, proceed as follows:
⇒
⇒
PARAM
Param
Settings
Set up 1
Set up 2
Manual operation
First start up
Edit
Next E
Hold
3.52 mS/cm
Param
Edit
Next
Set up 2
E
Hold
Check systems
Limit switch
Data log
Contr. quick adj.
Controller settings
3.52 mS/cm
CODE
CHOICE
(default = bold)
INFO
M1
off
On
Select controller functions
!
Note!
You must activate the controller function
after
you have
configured the controllers in this menu branch.
M2
Batch 1-s. up
Batch 1-s. down
Batch 2-sided
Inline 1-s. up
Inline 1-s. down
Inline 2-sided
Select the process type,
which describes your process.
1-s. = one-sided:
The control is either "up"
or
"down".
Two-sided
: The control is "up"
and
"down". You can only
select this function if you have defined two controllers
(in the "Contacts" menu and/or via the current output).