![Endress+Hauser Mycom S CLM 153 Operating Instructions Manual Download Page 90](http://html1.mh-extra.com/html/endress-hauser/mycom-s-clm-153/mycom-s-clm-153_operating-instructions-manual_2408551090.webp)
8 Troubleshooting
Mycom S CLM 153
90
EHauser
E072
Failure
Polarisation error 1
Clean sensor. Use higher cell
constant.
E073
Failure
Polarisation error 2
yes
no
no
E074
Failure
Temperature out of alpha table 1
Check measurement and tables for
plausibility;
if necessary, adjust or extend table.
yes
no
no
E075
Failure
Temperature out of conc table 1
yes
no
no
E076
Failure
Cond out of conc table 1
yes
no
no
E077
Failure
Temperature out of alpha table 2
Check measurement and tables for
plausibility;
if necessary, adjust or extend table.
E078
Failure
Temperature out of conc. table 2
E079
Failure
Cond out of conc. table 2
E080
Funct.
check
Range for current
output 1 too small
Increase measuring range span for
current output assignment
no
no
no
E081
Funct.
check
Range for current
output 2 too small
no
no
no
E100
Funct.
check
Current simulation active
Check if functions were consciously
selected
no
no
no
E101
Funct.
check
Service function active
no
no
no
E106
Funct.
check
Download active
Wait for download to end.
no
no
no
E116
Failure
Download error
Repeat download.
no
no
no
E117
Failure
DAT updownload error
Check with other DAT memory
module; when writing to DAT: repeat
write process
yes
no
–
–
E152
Mainte-
nance
PCS circuit 1 alarm
Conductivity sensor defective or
totally soiled; measured water flow in
bypass interrupted;
air cushion in assembly; measuring
line interrupted
no
no
no
E153
Mainte-
nance
PCS circuit 2 alarm
no
no
no
E154
Mainte-
nance
USP error 1
Conductance too high, check
process.
Check temperature for plausibility.
no
no
E155
Mainte-
nance
USP temp error 1
no
no
E156
Mainte-
nance
USP error 2
no
no
no
E157
Mainte-
nance
USP temp error 2
no
no
E171
Mainte-
nance
Current/resistance input 1 below
range
Measure input signal.
Permitted: 4 ... 20 mA
Resistance input: see controller
configuration (feedback) also
no
no
E172
Mainte-
nance
Current/resistance input 1 above
range
no
no
E173
Mainte-
nance
Current input 2 below range
Cause is the connected device or the
wiring.
no
no
E174
Mainte-
nance
Current input 2 above range
no
no
Error no.
NAMUR
class
Error message
Possible causes / measures
Alarm
contact
Error
current
Automatic
cleaning
start
Fact.
User
Fact.
User
Fact.
User