6 Commissioning
Mycom S CLM 153
64
EHauser
MD5
act. mA value:
____ mA
Assign a value for y = 0%
Drive the valve to y = 0 %.
The current current value is displayed. You can change
the valve position either manually or by pressing the
arrow keys on the transmitter. Confirm the position for y
= 0 % by pressing the "E" key.
!
Note!
If you cannot change it using the arrow keys, please
check the "Actuators" menu (Field 165) to see if the
relays have been assigned to valve control.
MD6
act. mA value:
____ mA
Assign a value for y = 100%
Drive the valve to y = 100%.
Proceeding as in the previous field.
Characteristic:
ME1
Constant characteristic
Segmented characteristic
Characteristic type selection
Constant characteristic :
Corresponds to a constant
control gain.
Segmented characteristic :
Corresponds to a range-
dependent control gain.
ME2
Setpoint
St.ntr. zone
End zone
K
R
1
K
R
2
1000 mS/cm
800 mS/cm
1500 mS/cm
200 mS/cm
200 mS/cm
Characteristic values for constant characteristic
(constant control gain) ; K
R
Setpoint
: The value which should be set.
St. ntr. zone:
Start neutral zone
End ntr. zone:
End neutral zone
K
R
1
(only with alkali dosing): Modulation gain for alkali
dosing
K
R
2
(only with acid dosing): Modulation gain for acid
dosing
ME3
Setpoint
St.ntr. zone
End zone
O.pnt. X1
O.pnt.Y1
O.pnt. X2
O.pnt.Y2
Ctrl.pnt. 1
Ctrl.pnt. 2
1000 mS/cm
990 mS/cm
1010 mS/cm
900 mS/cm
0.20
1100 mS/cm
-0.20
800 mS/cm
1200mS/cm
Characteristic values for segmented characteristic
(range-dependent control gain)
Setpoint
: The value which should be set.
St. ntr. zone:
Start neutral zone
End ntr. zone:
End neutral zone
Optimisation point 1 and 2:
Entry with x and y
coordinates
Control point 1
: The dosing is 100 % alkali for
measuring values < control point 1.
Control point 2
: The dosing is 100% acid for measuring
values > control point 2.
ME4
Rapid process
Standard process
Slow process
User settings
Select process character
If you have no experience in setting control
parameters, the defaults
rapid
/
standard
/
slow process
are intended as an aid to adapting the controller
behaviour to the process. Select a default and use the
"controller simulation" (see below) to check if these
settings are relevant for your process.
Enter all the characteristic values yourself with the
user
settings
.
ME5
K
R
1 =
K
R
2 =
Tn 1 =
Tn 2 =
Tv 1 =
Tv 2 =
Characteristic values for user settings:
(
K
R
1 and
K
R
2 only with linear characteristic;
Index 1 only for alkali dosing,
Index 2 only for acid dosing)
K
R
1
: Modulation gain for alkali dosing
K
R
2
: Modulation gain for acid dosing
Tn
: integral action time
Tv
: derivative action time
CODE
CHOICE
(default = bold)
INFO