ER5000
—
96
Installation Variations
Feedback Wiring Variations
Three Wire Transducer
The correct wiring for three wire transducers is shown in Figure 32.
TRANSDUCER
VIOLET
BLACK
YELLOW
ORANGE
TAN
+ SUPPLY
+ OUTPUT
COMMON
Figure 32: Three Wire Transducer Wiring
WARNING
The controller must be disconnected from the power supply before
any additional wiring or change to jumper configuration is
performed. Do not reconnect the power supply until all additional
wiring connections have been made and are properly installed.
Refer to Table 15 to verify correct wiring.
Table 15: Wiring for Three Wire Transducer
J3 Pins
Wire Color
Function
1
brown
+setpoint input
2
red
-setpoint input
3
orange
+feedback input
4
yellow
-feedback input
5
green
-RS485 network connection
6
blue
+RS485 network connection
7
violet
+24V DC power
8
gray
24V return (power ground)
9
white
+5V output (5 mA max.)
10
black
analog signal/board ground
*
11
*
pink
analog signal output
(active in Enhanced “F” models ONLY)
12
tan
analog signal/board ground
NOTE
NOTE
CAUTION
CAUTION
WARNING
WARNING
Check that
Jumper J6
(refer to
Figure 19
) is installed for
4–20 mA operation and removed for 1–5V operation. There is no jumper
on the 0–10V ER5000 models.
Summary of Contents for Tescom ER5000 Series
Page 2: ...2 Safety Installation Operations Precautions ...
Page 9: ...9 Table of Contents ...
Page 14: ...14 Features and Specifications ...
Page 25: ...25 What s New ...
Page 29: ...29 How It Works ...
Page 44: ...44 Glossary of Terms ...
Page 57: ...57 Getting Started ...
Page 76: ...76 Installation Variations ...
Page 111: ...111 The ERTune Program ...
Page 116: ...116 The ERTune Program Basic Features ...
Page 187: ...187 The ERTune Program Power User ...
Page 196: ...196 ER5000 Software Development Support ...
Page 202: ...202 Troubleshooting ...
Page 221: ...221 Internal Variables ...
Page 236: ...236 Certifications and Warranty ...
Page 241: ...241 Appendix A Setting up the ERTune Program on Windows 8 PCs ...