Installation Variations
Switch Feedback Control to a Second Feedback Source (cont.)
WARNING
The controller must be disconnected from the power supply before
any additional wiring or change to jumper configuration is
performed. Do not reconnect the power supply until all additional
wiring connections have been made and are properly installed.
This feature is part of
The Power User Tab
and is accessed in
The
Additional ER Settings Panel
. It allows the ER5000 to maintain
optimal control over different pressure ranges.
Transducers recommended for use with the ER5000 have an
accuracy of 0.1% of their full range, so transducers with a smaller
range have greater accuracy within that range.
In an application where the full range is 2,000 psig / 138 bar, but
where the 0 –500 psig / 0– 35 bar range is critical, a
single 2000 psig / 138 bar transducer has an accuracy of
+/- 2 psig / 0.14 bar across the entire range of the application.
Switching the feedback between a 500 psig / 35 bar transducer for
the critical range and the 2000 psig / 138 bar transducer for the
rest of the range, improves the accuracy within the critical range
to +/- 0.5 psig / 0.03 bar.
NOTE
NOTE
CAUTION
CAUTION
WARNING
WARNING
The wiring shown in
Figure 39
on the previous page is for two
wire transducers. Refer to
Figure 32
and
Figure 33
, respectively, for
correct wiring of three wire and four wire transducers.
Wiring Variations for Additional Functions
Monitoring Additional Analog Inputs
The ER5000 can monitor signals from a number of analog sources,
as well as monitoring the state of internal variables, during normal
system operation. This is useful for data acquisition to perform
trend analysis on the system. The two transducers (e.g., with
outputs P1 and P2) shown in
Figure 39
on the previous page
can be continuously monitored by a PC program such as the
ERTune™ program.
All ER5000 models can monitor two analog signals: the analog
setpoint and external feedback. “F” model ER5000s can monitor
two additional analog signals: the Auxiliary Input #1 and Auxiliary
Input #2.
NOTE
NOTE
CAUTION
CAUTION
WARNING
WARNING
Auxiliary Input #2 doubles as the Profile Start/Stop input. If you
are monitoring this input, you should change its toggle level from the
default value of 2050 to the maximum value of 4095. This will prevent the
Profile from running. The toggle level is set by adjusting variable #86
(ID_AD_EXTRA2_TOGGLE). Refer to
Internal Variables
for
more information.
Summary of Contents for Tescom ER5000 Series
Page 2: ...2 Safety Installation Operations Precautions ...
Page 9: ...9 Table of Contents ...
Page 14: ...14 Features and Specifications ...
Page 25: ...25 What s New ...
Page 29: ...29 How It Works ...
Page 44: ...44 Glossary of Terms ...
Page 57: ...57 Getting Started ...
Page 76: ...76 Installation Variations ...
Page 111: ...111 The ERTune Program ...
Page 116: ...116 The ERTune Program Basic Features ...
Page 187: ...187 The ERTune Program Power User ...
Page 196: ...196 ER5000 Software Development Support ...
Page 202: ...202 Troubleshooting ...
Page 221: ...221 Internal Variables ...
Page 236: ...236 Certifications and Warranty ...
Page 241: ...241 Appendix A Setting up the ERTune Program on Windows 8 PCs ...