Volume Flow Cutoff
:
10
l/sec
Result:
•
If the volume flow rate drops below 15 l/sec but not below 10 l/sec:
—
The mA Output will report zero flow.
—
The Frequency Output will report the actual flow rate, and the actual flow rate will be used in all
internal processing.
•
If the volume flow rate drops below 10 l/sec, both outputs will report zero flow, and 0 will be used in all
internal processing.
4.4 Configure Gas Standard Volume (GSV) flow
measurement
The gas standard volume (GSV) flow measurement parameters control how gas standard volume flow is
measured and reported.
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. Choose one
or the other.
Related information
Configure Volume Flow Type for gas applications
Configure Standard Gas Density
Configure Gas Standard Volume Flow Measurement Unit
Configure Gas Standard Volume Flow Cutoff
4.4.1 Configure Volume Flow Type for gas applications
Display
Menu
>
Configuration
>
Process Measurement
>
Flow Variables
>
Volume Flow Settings
>
Flow Type
>
Gas
ProLink III
Device Tools
>
Configuration
>
Process Measurement
>
Flow
>
Volume Flow Type
>
Gas Standard
Volume
Field Communicator
Configure
>
Manual Setup
>
Measurements
>
Optional Setup
>
GSV
>
Volume Flow Type
>
Standard Gas
Volume
Volume Flow Type
controls whether liquid or gas standard volume flow measurement will be used.
Restriction
Gas standard volume measurement is incompatible with the following applications:
•
API referral
•
Concentration measurement
•
Advanced Phase Measurement
For these applications, set
Volume Flow Type
to Liquid.
Configure process measurement
Configuration and Use Manual
April 2019
MMI-20048166
32