The readings do not need to match exactly. If the values are slightly different, you can correct
the discrepancy by trimming the output.
e) Click
UnFix mA
.
f) Enter
20
in
Fix to:
.
g) Click
Fix mA
.
h) Read the mA current at the receiving device and compare it to the transmitter output.
The readings do not need to match exactly. If the values are slightly different, you can correct
the discrepancy by trimming the output.
i) Click
UnFix mA
.
2. Test the Frequency Output(s).
a) Choose
Device Tools
>
Diagnostics
>
Testing
and select the frequency output to test.
b) Enter the frequency output value in
Fix to
.
c) Click
Fix FO
.
d) Read the frequency signal at the receiving device and compare it to the transmitter output.
e) Click
UnFix FO
.
3. Test the Discrete Output(s).
a) Choose
Device Tools
>
Diagnostics
>
Testing
>
Discrete Output Test
.
b) Set
Fix to:
to ON.
c) Verify the signal at the receiving device.
d) Set
Fix to:
to OFF.
e) Verify the signal at the receiving device.
f) Click
UnFix
.
Postrequisites
•
If the mA Output readings are within 20 microamps of the expected values, you can correct this
discrepancy by trimming the output.
•
If the discrepancy between the mA Output readings is greater than 20 microamps, or if at any step the
reading was faulty, verify the wiring between the transmitter and the remote device, and try again.
15.15.3 Perform loop tests using the Field Communicator
Procedure
1. Test the mA Output(s).
a) Choose
Service Tools
>
Simulate
>
Simulate Outputs
and select the mA output to test.
b) Select
4 mA
.
Configuration and Use Manual
Troubleshooting
MMI-20048166
April 2019
Configuration and Use Manual
191